Red Seal Pass
Red Seal Trade Guide · Gasfitter – Class B

Red Seal Gasfitter – Class B Practice Test — 10 Free Questions

Red Seal Pass is an independent Canadian practice site for the Gasfitter – Class B exam: 1,000 practice questions weighted to the official blueprint and rebuilt in 2026 to the latest exam trends, with every answer explained. The 10-question quiz on this page is free, with no sign-up. A full 100-question, 4-hour timed mock exam is $19.99 CAD, and full study passes start at $39.99 CAD/month ($89.99 CAD for 3 months, backed by our 7-Day Money-Back Guarantee). The real exam has 100 questions and a 70% pass mark.

⚡ Start the Free 10-Question Quiz Below ↓ View Study Plans

Preparing for the Red Seal Gasfitter – Class B exam

The Red Seal (Interprovincial) Gasfitter – Class B exam tests everything a working gasfitter needs: gas piping and tubing, venting and combustion air, burner controls and flame safeguards, propane storage, pressure testing and purging, and appliance start-up and service. Trying to memorize a thousand questions the night before rarely sticks. Research on the Ebbinghaus forgetting curve shows that spaced review holds knowledge better than cramming.

Red Seal Pass gives you a smarter path: a focused set of new questions each day, automatic review of the ones you miss, and clear explanations so you learn why, not just what.

🛡️ Free-Until-You-Pass Guarantee — buy the 6-Month Pass ($89.99 CAD), backed by our 7-Day Money-Back Guarantee and free access extension until you pass.

📥 Free Printable 30-Question Gasfitter – Class B Mock Exam PDF

Download our 30-question sample mock exam PDF with complete step-by-step answer keys and a blueprint breakdown.

Official Gasfitter – Class B exam blueprint

Published by red-seal.ca for the 100-question Interprovincial exam. These weightings decide how many questions you face in each area, so they decide where your study time belongs.

Major Work Activity Questions Share
MWA A: Performs common occupational skills 7 7.0%
MWA B: Installs fuel piping and tubing systems 14 14.0%
MWA C: Installs venting and air supply systems 15 15.0%
MWA D: Installs controls and electrical systems 15 15.0%
MWA E: Installs and converts fuel systems, appliances and ancillary equipment 15 15.0%
MWA F: Tests and commissions fuel systems, appliances and ancillary equipment 16 16.0%
MWA G: Services fuel systems, appliances and ancillary equipment 18 18.0%
Total 100 100%

Exam time 4 hours · pass mark 70%. Source: red-seal.ca official exam breakdown.

10-Question Gasfitter – Class B Quick Readiness Quiz — with Full Worked Answers

No sign-up and no email required. Take this 5-minute diagnostic quiz to test your current exam readiness. Every answer below includes complete code citations and worked steps — the same standard as the other 990 questions in the full bank.

⚡ Interactive Readiness Quiz
Click any option (A–D) below to test yourself & reveal the worked explanation.
Question 1 of 10
You are replacing an old cast-iron boiler in the basement of a 1950s apartment block in Winnipeg. While checking how the new vent connector will meet the breeching, you pull back a corner of the grey, chalky wrap on the breeching and it crumbles in your hand. The owner does not know what the wrap is made of, and the demolition of the old breeching is booked for this afternoon. What should you do first?
A) Wet the wrap down, put on a dust mask and strip it off carefully in large pieces
B) Stop, keep others out of the area and report it so the wrap is sampled and tested
C) Cover the torn corner with duct tape and carry on with the demolition as booked
D) Vacuum the loose wrap with the shop vacuum, bag it and then start the demolition
Correct answer: B

A crumbling, unidentified wrap on old breeching may contain asbestos, so the work stops, the area is kept clear and the hazard is reported to the owner and supervisor so a qualified person can sample it before anything else is disturbed. Option A treats the wrap as a do-it-yourself removal with a dust mask, which is not respiratory protection for asbestos and is not a removal procedure. Option C hides the damage and still lets the demolition disturb the material. Option D uses an ordinary shop vacuum, which blows fine fibres back into the room. A and D both remove the wrap before anyone knows what it is.

Question 2 of 10
You are joining 2 in. polyethylene gas pipe with a mechanical stab-type coupling on a repair in Kingston. The coupling manufacturer's instructions call for the pipe end to be cut square and chamfered with the chamfering tool they supply before the pipe is pushed into the coupling up to the insertion depth mark. What is the chamfer for?
A) To ease the pipe end past the internal seal and grip ring so the seal is not cut or rolled on entry
B) To thin the pipe wall at the end so the coupling can be pushed on without needing to reach the depth mark
C) To remove the outer layer of the pipe so the coupling can fuse to the clean polyethylene underneath it
D) To show the insertion depth on the pipe end so the depth mark from the instructions does not need drawing
Correct answer: A

The chamfer lets the square edge slide past the O-ring seal and the gripping ring inside the coupling without cutting or rolling the seal. Option B treats the chamfer as a way to avoid full insertion, but the pipe still has to reach the depth mark. Option C describes scraping for an electrofusion fitting, but a mechanical coupling does not fuse. Option D confuses the chamfer with the depth mark, which is a separate step. B and D both wrongly link the chamfer to the depth mark.

Question 3 of 10
In an unfinished basement in Sault Ste. Marie, ON, soft copper tubing must run across the bottoms of the floor joists for several metres to reach a furnace. The inspector tells you the tubing that crosses the joists must be protected from damage and must not sag between them. How should you install this part of the run?
A) Hang the tubing loosely between joists with tie wire at every third joist
B) Staple the tubing tight to the bottom of each joist with wire staples
C) Fasten a wood running board to the joists and clip the tubing to it
D) Lay the tubing on top of the ductwork so it rests across the joists
Correct answer: C

A wood running board fastened across the joists gives the tubing continuous support and a solid backing that protects it. Option A lets the tubing sag between widely spaced wire hangers. Option B fastens tightly at each joist but leaves the spans between them unsupported and exposed, and staples can crush soft tubing. Option D uses ductwork as a support, which it is not. A and B both fasten to the joists but leave the spans between them open.

Question 4 of 10
The drawing for a combustion air duct in a Brandon, MB, school boiler room dimensions the first hanger rod 18 in. from the face of the wall, end to centre, and every following rod at 5 ft. centre to centre. You are marking the concrete deck with a tape hooked on the wall face. How far from the wall should you mark the third hanger rod?
A) 10 ft. 0 in.
B) 13 ft. 0 in.
C) 16 ft. 6 in.
D) 11 ft. 6 in.
Correct answer: D

The first rod is 18 in. from the wall, and the third rod is two centre-to-centre spaces beyond it: 18 + 2 x 60 = 138 in., or 11 ft. 6 in. Option A counts the two spaces from the wall and drops the 18 in. end-to-centre dimension. Option B adds the 18 in. twice. Option C counts three spaces instead of two, which is the location of the fourth rod. A and D differ only in the end-to-centre offset.

Question 5 of 10
The ladder diagram for a commercial burner at a laundry in Moncton shows the low gas pressure switch, the high gas pressure switch and the combustion air proving switch drawn one after another in a single line between L1 and the flame safeguard's running interlock terminal. While the burner is firing, the high gas pressure switch trips. What will the flame safeguard do?
A) Keep the burner firing and raise an alarm until the next call for heat
B) Close the fuel valves only if the other two switches open at the same time
C) De-energize the fuel valves at once and go to a safety shutdown
D) Drive the burner to low fire and keep it firing on the pilot alone
Correct answer: C

The three switches are in series, so any one of them opening breaks the running interlock circuit, and the safeguard drops the fuel valves at once and goes to safety shutdown. Option A lets the burner keep firing with gas pressure out of limits. Option B reads the switches as if they were in parallel, where all three would have to open. Option D keeps the pilot burning with the interlock circuit open, which the safeguard does not allow. A and D both keep some fuel burning after a safety switch has opened.

Question 6 of 10
A modulating combustion air damper actuator on a boiler in a Rouyn-Noranda, QC, mill takes a 4-20 mA signal from the boiler controller: fully closed at 4 mA and fully open at 20 mA. You are checking whether the actuator follows the controller, and the loop reads 13.6 mA. Using actuator position % = (IS - FCS) / (FOS - FCS), what position should the damper be at?
A) 68 %, from 13.6 mA divided by 20 mA, leaving out the 4 mA zero
B) 40 %, from 20 mA less 13.6 mA, divided by the 16 mA span
C) 48 %, from 13.6 mA less 4 mA, divided by 20 mA instead of the span
D) 60 %, from 13.6 mA less 4 mA, divided by the 16 mA span
Correct answer: D

Position = (13.6 - 4) / (20 - 4) = 9.6 / 16 = 60 % open. Option A divides the raw signal by the top of the range and ignores the 4 mA live zero. Option B measures from the fully open end, which gives the percentage still closed, not the position open. Option C subtracts the zero from the signal but not from the range. C and D differ only in whether the span or the top value is used as the divisor.

Question 7 of 10
You are making up threaded steel joints on the liquid line from a bulk propane tank to the pump of an autogas dispenser at a service station in Lethbridge, AB. The truck holds several thread sealants left over from plumbing and mechanical jobs, and the joints will hold liquid propane at full tank pressure. Which joining compound should you select for these joints?
A) A thread compound that its maker lists as resistant to LP-gas
B) A general-purpose pipe dope rated for potable water and drains
C) Plumber's putty worked into the threads before making them up
D) A soft-setting gasket sealant rated for engine oil and coolant
Correct answer: A

Thread compounds on propane piping must be listed by their maker for LP-gas, because propane dissolves or washes out many ordinary sealants. Option B is rated only for water and drainage, so propane can break it down and open a leak path. Option C, plumber's putty, is a sealing putty for fixtures and is not a thread sealant for pressure piping. Option D is made for engine fluids, not for liquid propane under pressure. B and D are both rated for other fluids and differ only in which ones.

Question 8 of 10
You are purging the newly tested line to a range and dryer in an Oshawa house, running the purge gas through a hose out a basement window as the inspector allows for this small line. The homeowner is upstairs, and the basement lights are off. The purge will take a few minutes. What should you do about ignition sources while gas is being released?
A) Switch lights and fans on and off as needed to see and air out the basement
B) Keep flames and sparks away, and do not switch any electrical device on or off
C) Light a range burner at once, so gas reaching the room is burned as it arrives
D) Keep flames away, and run a corded fan near the hose outlet to spread the gas
Correct answer: B

While gas is being released, flames, sparks and electrical switching are kept away, since a switch can spark as it opens or closes. Option A switches devices during the purge. Option C brings a flame into a space where gas may be present. Option D keeps flames away but places a running electric fan in the gas at the outlet. B and D differ in whether an electrical device is used near the gas.

Question 9 of 10
You are commissioning a new natural gas boiler in a three-storey Victoria apartment building. The highest radiator is 35 ft above the boiler's fill valve, and the engineer wants 5 psi at the top of the system so air can be vented there. Using 0.433 psi per foot of water head, what cold fill pressure should you set on the pressure-reducing valve?
A) About 20 psig, from 35 x 0.433 plus the 5 psi at the top
B) About 15 psig, from 35 x 0.433 without the 5 psi at the top
C) About 10 psig, from 35 x 0.433 minus the 5 psi at the top
D) About 86 psig, from 35 / 0.433 plus the 5 psi at the top
Correct answer: A

The static head is 35 x 0.433 = 15.2 psi, and adding the 5 psi wanted at the top gives about 20 psig at the fill valve. Option B fills only to the static head, leaving no pressure at the top. Option C subtracts the 5 psi instead of adding it. Option D divides by 0.433 instead of multiplying, which turns feet into a much larger figure. B and C both start from the right head but mishandle the 5 psi.

Question 10 of 10
A packaged hot water boiler in a Saskatoon school locks out on its low gas pressure switch each time it drives to high fire. Your manometer on the gas train inlet reads 7.0 in. w.c. static and falls to 3.2 in. w.c. at high fire. The low gas pressure switch is set at 4.0 in. w.c., the setting written on the burner's start-up sheet. What should you conclude and do?
A) The switch is set too high for this supply; lower its setting below the high-fire reading so the boiler stays on
B) The supply cannot hold pressure under load; check the upstream regulator and pipe sizing before touching the switch
C) The supply is fine because static pressure is above the setting; replace the low gas pressure switch as faulty
D) The supply cannot hold pressure under load; turn up the boiler's own train regulator until high fire reads correctly
Correct answer: B

Pressure that holds when static but sags well below the switch setting at high fire shows the supply is drooping under flow, so the upstream regulator and pipe sizing are checked; the switch is tripping as designed. Option A lowers a safety setting taken from the start-up sheet to hide a supply problem. Option C judges the supply by static pressure alone and blames a switch that is working. Option D turns up the train regulator, which sits downstream of the inlet reading and cannot add pressure to the supply ahead of it. B and D reach the same conclusion and differ only in where the fix is made.

A 4-week study plan for the Gasfitter – Class B exam

18 new questions a day is the pace the platform sets, because spacing beats cramming. Over four weeks that is about 504 questions, and the order below follows the official weightings above.

Booking the Gasfitter – Class B exam where you live

Eligibility and booking are handled by your province, not by the Red Seal program itself. Start here:

The full question bank

1000 Gasfitter – Class B questions, every one explained

Ready to go beyond the 10-Question Readiness Quiz for Gasfitter – Class B? To keep preparing for your 100-question Red Seal exam, unlock the full 1000-question bank with automatic Spaced Repetition (Ebbinghaus) and an AI tutor that explains every missed question.

🛡️ Instant Access · One-Time Payment · Free-Until-You-Pass Guarantee Backed

Frequently asked questions

How many questions are on the Red Seal Gasfitter – Class B exam?

The Interprovincial Red Seal Gasfitter – Class B exam has 100 multiple-choice questions, a 4-hour limit and a 70% pass mark, per the official exam breakdown on red-seal.ca.

Can I sample practice questions before subscribing?

Yes. You can download a free 30-question sample mock exam PDF with full step-by-step answer explanations. A subscription unlocks all 1000 questions, spaced-repetition review, and AI tutoring.

What's the best way to study for the Red Seal exam?

Consistent daily practice beats cramming. Our founder sat the Red Seal exam in 2026; read what the real exam asked and what we changed.

What does a subscription cost?

We offer a 1-Mock Exam Ticket ($19.99 CAD one-time), a Monthly Pass ($39.99 CAD/month), and a 6-Month Pass ($89.99 CAD one-time) with our 7-Day Money-Back Guarantee and Free-Until-You-Pass Guarantee. All plans include daily adaptive practice, spaced-repetition review, and AI Journeyperson Tutor coaching.

In-Depth Gasfitter – Class B Study Articles & Concept Guides

Deep dives into specific code requirements, safety rules and exam strategy, written from the official blueprint and Canadian code references:

2026-11-19 · Exam Blueprint Guide
Red Seal Gasfitter Class B Exam Guide (2026): 100 Questions & CSA Codes
2026 Red Seal Gasfitter – Class B exam guide: official 100-question MWA A–G weighting, CSA B149.1/B149.2/B149.3 code focus, key formulas & study plan.

Red Seal Exam Guides by Province

Other Red Seal practice exams